Tate Strut is a strong, galvanized steel profile with a white painted finish. Uniquely integrated welded flanges support tiles, light fixtures and return air grilles—removing the need for two separate ceiling systems. The continuous open channel slot allows for full flexibility when suspending cable trays, bus bars, and other heavy accessories from the structural ceiling. Both strut main runners and structural tees are pre-drilled for infill connections based upon application specifications.
Refer to the table below for load capacities and corresponding deflections based on various span lengths
SPAN (cm) |
Max Point Load at Yield Point1 (kN) |
Max Deflection at Yield Point (cm) |
Max Point Load at Various Deflections (kN) | Max Uniform Load (kN/m) |
Max Uniform Load (kN/m2) |
||
---|---|---|---|---|---|---|---|
SPAN/180 | SPAN/240 | SPAN/360 | |||||
120 | 7.792 | 0.41 | 7.79 | 7.79 | 6.29 | 3.25 | 5.41 |
150 | 7.792 | 0.81 | 7.79 | 6.04 | 4.02 | 2.60 | 3.46 |
180 | 7.50 | 1.34 | 5.59 | 4.20 | 2.80 | 2.09 | 2.32 |
210 | 6.49 | 1.84 | 4.11 | 3.08 | 2.05 | 1.55 | 1.47 |
240 | 5.65 | 2.40 | 3.15 | 2.36 | 1.57 | 1.18 | 0.98 |
270 | 4.99 | 3.01 | 2.48 | 1.86 | 1.25 | 0.92 | 0.69 |
300 | 4.52 | 3.74 | 2.01 | 1.51 | 1.01 | 0.76 | 0.50 |
1. Maximum point load locations are to be no less than the length of the strut span in any given direction.
2. Maximum point loads are limited by the turnbuckle connections to strut. Turnbuckles are required to be within 300mm of a main runner splice.
SAFS is an approved Victorian distributor for Tate access flooring systems. We work on projects ranging from $2 000 and a few days’ work to $2 000 000 work carried out over several months.