The Posilock understructure system provides self-engagement and positioning of the raised floor panels without the need for stringers.
System Performance Criteria (Tested on Actual Understructure*)
System Type | System Weight (lbs/ft2) |
Static Loads | Rolling Loads | Impact Loads |
||||||
---|---|---|---|---|---|---|---|---|---|---|
Panel | Understructure | Design Loads1 |
Minimum Ultimate Loads |
Safety Factor (min 2.0)2 |
10 Passes |
10,000 Passes |
||||
ConCore 800 | Cornerlock | 48 kg/m2 | 3.5 kN | 8.8 kN | PASS | 3.5 kN | 2.5 kN | 0.6 kN |
*All tests are performed using CISCA's Recommended Test Procedures for Access Floors with the exception of Design Load
1. System Design Load is based on permanent set ≤ 0.010” and is verified by loading panels in accordance with the CISCA concentrated load method but with panels installed on actual understructure instead of steel blocks. (Testing on blocks does not represent performance of an actual installation.) Ultimate, Rolling, and Impact Load tests are performed using CISCA Test Procedures.
2. Safety Factor is Ultimate Load divided by Design Load.