STONEWORKS floor panels eliminate the need for finish lamination as the high-end architectural finish and the structural integrity of the panel is combined into a single integrated panel. STONEWORKS panels are engineered to meet Tate Standards per CISCA testing methods.
System Performance Criteria (Tested on Actual Understructure*)
System Type | System Weight (lbs/ft2) |
Static Loads | Rolling Loads | Impact Loads |
||||
---|---|---|---|---|---|---|---|---|
Panel | Understructure | Design Loads1 |
Minimum Ultimate Loads |
Safety Factor2 |
10 Passes |
10,000 Passes |
||
STONEWORKS® Panel |
4' Heavy-Duty Bolted Stringer |
15.75 lbs/ft2 |
1500 lbs | 2160 lbs | 1.44 | 1250 lbs | 1000 lbs | 150 lbs |
*All tests are performed using CISCA's Recommended Test Procedures for Access Floors with the exception of Design Load
1. System Design Load is based on permanent set ≤ 0.010” and is verified by loading panels in accordance with the CISCA concentrated load method but with panels installed on actual understructure instead of steel blocks. (Testing on blocks does not represent performance of an actual installation.) Ultimate, Rolling, and Impact Load tests are performed using CISCA Test Procedures.
2. Safety Factor is Ultimate Load divided by Design Load.
SAFS is an approved Victorian distributor for Tate access flooring systems. We work on projects ranging from $2 000 and a few days’ work to $2 000 000 work carried out over several months.